On September 29, 2022, ANSI released the latest revision of the ANSI/TIA-568.3-E, Optical Fiber Cabling and Components Standard. A couple primary introductions of interest to most users will be the addition of two new connectivity (polarity) methods for array (MPO)-based duplex applications.
The revision also introduced revised guidance on pinning of connectors to better support future transition to end-to-end array systems.
Prior to the release of this revision of the Standard, connectivity methods for array-based duplex applications were limited to Methods A, B & C – each having its own strengths and weaknesses. ANSI/TIA-568.3-E introduced two new “universal” methods: U1 and U2. The advantage of these new methods is having the commonality components of Method B without the need for unique MPO*-to-LC modules on each end. Customers can now use the same MPO-to-LC modules and duplex patch cords on either end of the channel in conjunction with a Type-B trunk – thus simplifying deployments.
Methods U1 and U2 both use Type-B array trunks and A-to-B duplex patch cords. Where they differ is Method U1 uses Type-A (Key-Up to Key-Down) array adapters and Type-U1 fiber transitions which Method U2 uses Type-B (Key-Up to Key-Up) array adapters and Type-U2 fiber transitions as show below in Table 1 and Figure 1:
Connectivity Method | Array Trunk Cable | Array Adapter | Fiber Transition | Duplex Patch Cord |
---|---|---|---|---|
U1 | Type-B | Type-A | Type-U1 | A-to-B |
U2 | Type-B | Type-U2 |
Table 1: New Duplex Connectivity Methods
The key advantage of Method U1 vs Method U2 is that the use of Type-A adapters enables support of both multimode and singlemode applications as standard singlemode MPO connectors utilize opposing angled physical contact (APC) end faces which are necessary to provide the more stringent return loss requirements of singlemode applications.
Additionally, Method U1 MPO-to-LC modules are ideal for use as a breakout or aggregation module for optical transceiver applications as shown below in Figure 2.
Additional MPO connector pinning guidance was also introduced in this new revision of the Standard to better enable future transition of an array-based duplex system to an end-to-end array system. When mating MPO connectors – which use alignment pins – it is a requirement that one plug is pinned and the other plug is unpinned. As MPO active equipment ports are pinned, they accept only unpinned plugs.
Therefore, an optimally designed array-based duplex system intended to support a future transition to an end-to-end array system should specify the following as illustrated in Figures 3 and 4:
Due to all the above reasons, Siemon continues to act as a trusted advisor to our clients and recommends Base-8 systems for new installations and will continue to only recommend solutions that solve problems, make sense for a given customer application, and are cost-effective.
With the release of Siemon’s new LightVerse® fiber connectivity platform, Siemon offers Type-U1 MPO-to-LC modules with unpinned MPO connectors in both Base-8 and Base-12 as the standard offering and recommends the use pinned array trunks ensuring the simplest design and implementation of array-based duplex systems, breakout applications and future transition to end-to-end array systems.
* MPO is a generic reference – Siemon uses MTP connectors which are a premium MPO connector for all array connectivity products
Dave Valentukonis
North America Technical Services Manager, Siemon
Dave Valentukonis joined Siemon in 1995 and has held positions in Technical Support and Product Management. He is currently the North American Technical Services Manager where he oversees an experienced team of product, application, training, and technology experts that help Siemon customers navigate a diverse and rapidly changing market. He is a BICSI RCDD/NTS and an active member of TIA.